產(chǎn)品內(nèi)容介紹
A-B 80190-280-02-R控制數(shù)據(jù)輸入輸出
設(shè)置節(jié)點地址配置選項模塊節(jié)點地址有四種方法:
?節(jié)點地址開關(guān)-在處理簡單、具有其他產(chǎn)品的隔離網(wǎng)絡(luò)(例如192.168.1.xxx)通過交換機(jī)設(shè)置其IP地址,無需從在網(wǎng)絡(luò)之外,您更喜歡簡化的節(jié)點尋址方法。
驅(qū)動器通電時讀取三個旋轉(zhuǎn)開關(guān),并表示從上到下三個十進(jìn)制數(shù)字(見圖2)。當(dāng)設(shè)置為有效地址(001…254),選項模塊將使用該值作為下限其IP地址的八位字節(jié)(192.168.1.xxx,其中xxx=旋轉(zhuǎn)開關(guān)設(shè)置),以及子網(wǎng)掩碼255.255.255.0和網(wǎng)關(guān)地址
當(dāng)交換機(jī)設(shè)置為001或網(wǎng)關(guān)地址為192.168.1.1時,為0.0.0.0
當(dāng)開關(guān)設(shè)置為002…254時。此外,設(shè)備的設(shè)置參數(shù)05-[Net Addr Sel]自動忽略。
有關(guān)所有可能的開關(guān)設(shè)置和它們的相關(guān)描述。
?選項模塊參數(shù)-當(dāng)您想要更靈活地設(shè)置網(wǎng)絡(luò)節(jié)點地址,或者需要使用網(wǎng)關(guān)在控制網(wǎng)絡(luò)外部通信。
要使用參數(shù)作為IP地址的源,節(jié)點地址開關(guān)必須設(shè)置為001…254或888以外的值,以及設(shè)備參數(shù)05-[Net Addr Sel]必須設(shè)置為“1”(參數(shù))。IP地址,子網(wǎng)掩碼和網(wǎng)關(guān)地址將來自使用關(guān)聯(lián)的選項模塊參數(shù)。有關(guān)詳細(xì)信息,請參見使用選項第36頁的模塊參數(shù)。
BOOTP-當(dāng)您想要配置臨時IP時,請使用BOOTP選項模塊的地址、子網(wǎng)掩碼和網(wǎng)關(guān)地址BOOTP服務(wù)器。
要使用BOOTP作為IP地址的源,節(jié)點地址開關(guān)必須設(shè)置為001…254或888以外的值,并且設(shè)備參數(shù)05-[Net Addr Sel]必須設(shè)置為“2”(BOOTP)。?DHCP(動態(tài)主機(jī)配置協(xié)議)-使用DHCP設(shè)置,當(dāng)您希望與配置IP地址、子網(wǎng)掩碼和網(wǎng)關(guān)地址時的BOOTP用于使用DHCP服務(wù)器的選項模塊。
使用DHCP作為源對于IP地址,節(jié)點地址開關(guān)必須設(shè)置為其他值001…254或888,且設(shè)備參數(shù)05-[Net Addr Sel]必須為設(shè)置為“3”(DHCP)。如果PowerFlex 750系列驅(qū)動器連接到Stratix 6000或Stratix 8000受管以太網(wǎng)交換機(jī),驅(qū)動器設(shè)置為BOOTP模式“端口動態(tài)IP地址分配”(Stratix 6000)或“DHCPpersistence”(Stratix 8000)功能將設(shè)置驅(qū)動器的IP地址。
有關(guān)更多詳細(xì)信息,請參閱Stratix 6000以太網(wǎng)網(wǎng)管交換機(jī)用戶手冊、出版物1783-UM001或Stratix 8000和Stratix 8300以太網(wǎng)管理交換機(jī)用戶手冊,出版物1783-UM003
Setting the Node Address
There are four methods for configuring the option module node address: ? Node Address Switches — Use these switches when working on a simple, isolated network (for example, 192.168.1.xxx) that has other products with switches to set their IP addresses, does not need to be accessed from outside the network, and you prefer a simplified node addressing method. The three rotary switches are read when the drive powers up, and represent three decimal digits from top to bottom (see Figure 2). When set to a valid address (001…254), the option module will use that value as the lower octet of its IP address (192.168.1.xxx, where xxx = rotary switch settings), along with a subnet mask of 255.255.255.0, and a gateway address of 0.0.0.0 when switches are set to 001, or a gateway address of 192.168.1.1 when switches are set from 002…254. Also, the setting for Device Parameter 05 - [Net Addr Sel] is automatically ignored. See Figure 2 and its accompanying table for all possible switch settings and their related descriptions. ? Option Module Parameters — Use option module parameters when you want more flexibility in setting up the network node address, or need to communicate outside the control network using a gateway. To use parameters as the source for the IP address, the Node Address switches must be set to a value other than 001…254 or 888, and Device Parameter 05 - [Net Addr Sel] must be set to “1” (Parameters). The IP address, subnet mask, and gateway address will then come from the values set using the associated option module parameters. For details, see Using Option Module Parameters on page 36.
BOOTP — Use BOOTP when you want to configure a temporary IP address, subnet mask, and gateway address for the option module using a BOOTP server. To use BOOTP as the source for the IP address, the Node Address switches must be set to a value other than 001…254 or 888, and Device Parameter 05 - [Net Addr Sel] must be set to “2” (BOOTP).
? DHCP (Dynamic Host Configuration Protocol)
— Use DHCP, the default, when you want additional flexibility and ease-of-use compared to BOOTP in configuring the IP address, subnet mask, and gateway address for the option module using a DHCP server. To use DHCP as the source for the IP address, the Node Address switches must be set to a value other than 001…254 or 888, and Device Parameter 05 - [Net Addr Sel] must be set to “3” (DHCP).If the PowerFlex 750-Series drive is connected to a Stratix 6000 or Stratix 8000 managed Ethernet switch and the drive is set for BOOTP mode, the “dynamic IP address assignment by port” (Stratix 6000) or “DHCP persistence” (Stratix 8000) feature will set the IP address for the drive. For more details, see the Stratix 6000 Ethernet Managed Switch User Manual, publication 1783-UM001 or the Stratix 8000 and Stratix 8300 Ethernet Managed Switches User Manual, publication 1783-UM003
公司主營產(chǎn)品圖展示